Wednesday, October 30, 2013

RSWHO Failed to show - RsLinx

If you got the problem on the RSLogix 5000 and RsLinxClassic cannot open the RSWHO.
The message appear if you click the button on the RSLogix 5000:


I get this popup whenever I open RSLinx Classic Lite.
If it matters/helps it's Revision: 2.54.00.11 CPR 9 SR1

Need register file C:\Program Files\Rockwell Software\RSCommon\RSOBSERVE.EXE



How to solve this problem:
1. On the computer click Start-->Settings-->ControlPanel-->AdministrativeTools

2. Next, double click on Services

3. Look for
Harmony in the Services list. Double click on
Harmony and then click on the down arrow and change Harmonys
Startup Type from Disable to Manual. 


Good Luck!!

Thursday, August 20, 2009

Quick Setup of PLC5 Ethernet Connection

General

These are some notes on how to quickly setup a simple network for use with a PLC-5 Ethernet
processor. Setup of a SLC5/05 is similar, except that a transceiver is not required.

The following hardware/software was used:

Allen-Bradley PLC5-40E

CentreCOM 210TS 10 Transceiver

Allen-Bradley RSLinx (Lite or better), Version 2.30.01

Allen-Bradley RSLogix5, Version 5.00.01

Microsoft Excel 2000

Step 1 - Physically Connect PLC5 to Network

The first step is to physically connect the PLC5 to your network. On the PLC5-40/E, the ethernet port is channel 2 and is also referred to as the AUI port. It is a 15-pin, female D-shell connection. My existing network is a 10 MPS thin net setup with several hubs connecting to a router. To go from the 15-pin connection on the PLC to the RJ-45 modular connection on the hub, a twisted pair transceiver (also called a MAU, medium access unit) is required. I used a CetreCOM 210TS that I bought for $10 on the internet. This plugs into the port on the PLC and a standard modular CAT 5 cable was used to connect this to the hub.

Step 2 - Setup PLC's Communications Parameters with RSLogix5

Start up RSLogix and connect to the processor using the DH+ and DH485 (serial port) connection. Double click on "Channel Configuration" under "Controller". Click on the "Channel 2" tab to reveal the parameters for the ethernet port. For a simple network (no subnets), the only parameters that are important are the IP address and the link ID number. Make sure that the "BOOTP Enabled" check box is not checked and enter the desired IP address. Enter an unused link ID number. The rest of the parameters can be left at their default values.

Step 3 - Verify the Physical Connection

This is an optional step to verify the physical link. You can skip this step if you're confident of your connection. From a computer on the same network as the PLC, ping the PLC's address. If everything is hooked up right, you will get an answer for each ping. You can use the DOS ping.exe program found in the "windows" directory or download a Windows-based ping program such as Alchemy Lab's Ping 1.0.

Step 4 - Setup RSLinx

Start up RSLinx (Lite or higher) and and go to Communications --> Configure Drivers. Then under the "available Drivers" list, select "Ethernet devices" and click on "AddNew". I usually use the default name. When the "Station mapping" window pops up, in the "Station" field, enter the same ID number you entered in RSLogix5. In the Host Name field, enter the same IP address as you entered in RSLogix5. Then hit the "Apply" button and you should be good to go.

Step 5 - Test the Connection

To test the connection, in RSLinx, go to Communications-->RSWho. Double click the ethernet connection and your PLC should show up. To go online, in RSLogix , go to Comms-->Who Active Go Online and select the PLC under the ethernet connection. Programming can be done using RSLinx Lite or better.

Thursday, July 30, 2009

DF1 to DH+ Passthru using WinLinx or RSLinx

For OLD Application...

SLC 5/04 processors (OS401 and greater) support DF1 to DH+ Passthru. With this feature, you can connect to a 5/04 processor through Channel 0 using the DF1 protocol and access any node on the DH+ network, regardless of the baud rate of the DH+ network. It is also possible to connect a modem to Channel 0 and connect to any node on the DH+ network via modems.

At this time only PanelView devices at FRN 3.3 or higher can be accessed using the SLC 5/04 passthru. Pre FRN 3.3 PanelViews do not recognize PCCC messaging which is the protocol used on the DH+ side of the SLC. An alternate bridge solution would be a 1770-KF2. The customer should consult their local distributor for other hardware, serial to DH+ bridge, solutions or firmware upgrades.

To use this functionality with the RSLogix 500 software, you need to use the following procedure:


PROCESSOR SETTINGS:

RSLogix500

1) Configure Channel 0 of the 5/04 processor for System Mode using Full-Duplex. This can be done by accessing the Channel Configuration Window and choosing the appropriate settings.

**Note the Passthru Link ID setting for Channel 1 (which is 2) and Channel 0 (which is 1). If channel's 1 and 0 have the same link ID's then RSLinx/RSWho will not see through to the DH+ network.








2) You must then access the Chan 0 Tab on the Processor Status File and disable the DH485 to DH+ Passthru and enable DF1 to DH+ Passthru by setting both S:34/0 AND S:34/5 high. Note: If you want to view active DH+ nodes in the 5/04 status table, S:34/1 must also be set.






The above settings must then be downloaded to the processor using either Winlinx or RSLinx. Once the program has been downloaded, comms drivers must be altered as detailed below to see the entire DH+ network. Also note that the driver verification in Winlinx and Auto-Configure in RSLinx will no longer function correctly since DF1 packets are being passed through Chan 1. Both functions will still determine the baud rate, but acknowledgements will no longer be received causing the error checking to fail.

COMMUNICATION SETTINGS:

WinLinx

The uLogic/KF3/CH0 driver was initially used to download the project to the 5/04. This driver must be deleted from Winlinx and the KF2/KE driver must be used instead. Be sure to set the correct baud rate and turn on the Don't Verify Settings radio button. Click OK to accept the driver changes. The SuperWho screen will poll address 1-77 and display any active DH+ nodes.






RSLinx v1.7

To download the program, recall that the Device Type option was initially set to SLC-CH0. Change this to KF2/KE and click on OK.







Select Communications > SuperWho and 'right-click' anywhere inside the Who screen and choose Configure SuperWho. In the dialog box, change the Station Update Mode from Graphical (default) to Normal and click OK. The resulting Who screen will begin polling from node 1 thru 77 octal and display all devices connected to the DH+ network.







Remember, the RSLogix500 Who configuration is separate from the RSLinx Who configuration. Be sure that the Normal mode is chosen in both configurations.

Note: RSLinx 1.7 requires that one of the nodes on the DH+ network be set to station 1. If none of the nodes are set to 1 nothing will appear in the SuperWho. This is not a requirement for RSLinx revision 2.1.


RSLinx v2.0

Once the program has been downloaded, in the driver configuration dialog, change the Device Type to 1770-KF2/1785-KE and click OK. Click Close to save the change. If Autobrowsing is enabled, the RSWho will automatically poll the DH+ network using your AB_DF1 driver.





Note: RSLinx 2.0 requires that one of the nodes on the DH+ network be set to station 1. If none of the nodes are set to 1 nothing will appear in the RSWho. This is not a requirement for RSLinx revision 2.1 (or higher).
#