The following ports are used in WinCC flexible Runtime:
Service | Port | |||
Web server | Access to internal HTML pages (HTTP) | 80 | ||
Access to internal HTML pages (HTTPS) | 443 (SSL) | |||
Sm@rtServer | Connection with the Sm@rtServer (access to the Sm@rtServer for downloading the Java applets with the Internet Explorer) | 5800 | ||
Connection with the Sm@rtServer (access to the Sm@rtServer with Internet Explorer for remote monitoring and operation) | 5900 | |||
OPC | ||||
OPC via DCOM | Server | Connection setup: | 135 | |
Communication | dynamic 1) | |||
Client | Communication | dynamic 1) | ||
OPC via XML (Client <=> Server) | 80 | |||
Printing | Printing of Windows CE panels via Ethernet | 1032 | ||
Archiving | Archiving on a server 2) | UDP | 137, 138 | |
TCP | 139 | |||
Miscellaneous | Transfer via Ethernet | Configuration PC | dynamic 1) | |
Panel | 2308 and 50523 | |||
Communication between | S7 controller | 102 | ||
Panel | dynamic 1) | |||
PROFINET IO communication 3) | 34964 | |||
E-mail (SMTP server) | 25 | |||
Modicon controller (Modicon channel MODBUS TCP/IP) | 502 |
The Microsoft Windows operating system automatically assigns the relevant service a free port that can be between Port 1024 and 65534. You must enable this area when using a firewall.
2) Archiving:
Requirement for archiving via an Ethernet network is that the server is enabled.
3) PROFINET
Communication via PROFINET must be activated in the "Control Panel", in the "PROFINET" Settings dialog.
Note:If you change the ports of the Sm@rtServer, you must change the links accordingly in the HTML pages used. More information on changing HTML pages is available in the Help system of WinCC flexible under "Example: Configuring an integrated web server".