QUESTION:
How do I replace a DP/DP coupler with the order no. 6ES7 158-0AD00-0XA0 with a DP/DP coupler with the order no. 6ES7 158-0AD01-0XA0?

ANSWER:

Compatibility
The DP/DP coupler with the order number 6ES7 158-0AD01-0XA0 is compatible to the DP/DP coupler with the order number 6ES7 158-0AD00-0XA0:

  • The diagnostic information for the sync and freeze mode for the coupler with the order number ...-0AD01-... has been improved in comparison to the DP/DP coupler with the order number ...-0AD00-... and correspondingly adapted to the PROFIBUS norm.
  • The DP/DP coupler with the order number ...-0AD01-... can be used as a replacement for predecessor modules. The design is compatible.

Exchanging the DP/DP coupler
Follow this procedure to exchange the DP/DP coupler. The individual steps are described below.

  • Transfer the switch settings
  • Dismantle the old DP/DP coupler
  • Mount the new DP/DP coupler

Transferring the switch settings

  1. Note the PROFIBUS addresses (DIL switch 1 to 64) from the old DP/DP coupler and set the identical PROFIBUS addresses on the new DP/DP coupler. The following applies:
DP/DP coupler (...-0AD00-...) = = DP/DP coupler (...-0AD01-...)
DP1 (DIL switch 1 bis 64) = = DP1 (DIL switch 1 bis 64)
DP2 (DIL switch1 bis 64) = = DP2 (DIL switch 1 bis 64)
Setting "0" = = Setting "OFF"
Setting "1" = = Setting "ON"
  1. Transfer the diagnostics settings from the old DP/DP coupler:
DP/DP coupler (...-0AD00-...) = = DP/DP coupler (...-0AD01-...)
DP1 (diagnostics) = = DP1 (DIA)
DP2 (diagnostics) = = DP2 (DIA)
Setting "0" = = Setting "OFF"
Setting "1" = = Setting "ON"

  1. Set the DIL switch "PS" (Power Supply). Only the new DP/DP coupler has a "PS" DIL switch with following settings:
    • PS (DP1) to “ON”: L+/M (PS1) is connected to DC 24 V
    • PS (DP2) to “ON”: L+/M (PS2) is connected to DC 24 V

We recommend the following procedure for switching to the new DP/DP coupler:

  • Connect the power supply for the DP/DP coupler to "PS (DP2)"
    (see section "Mounting the new DP/DP coupler", step 3).
  • Set the PS DIL switch (DP1) to "OFF".
  • Set the PS DIL switch (DP2) to "ON".
  1. Set the DIL switch "ADDR". Only the new DP/DP coupler has a "ADDR" DIL switch with following settings:
    • ADDR to “ON”: The DP/DP coupler gets the PROFIBUS address from STEP 7.
    • ADDR to “OFF”: The DP/DP coupler gets the PROFIBUS address from the DIL switch.

We recommend the following procedure for switching to the new DP/DP coupler:

  • Set the DIL switch on DP1 and DP2 to "OFF". This means that the PROFIBUS addresses will be read directly from the DIL switch.

Dismantling the old DP/DP coupler

  1. Turn the power supply for the DP/DP coupler off.
  2. Pull the bus connector plug out of the PROFIBUS DP interface.
  3. Pull out the power supply of the defective DP/DP coupler.
  4. Loosen the screws of the DP/DP coupler that secure the DP/DP coupler to the rail.
  5. Swing the DP/DP coupler off the rail.

Mounting the new DP/DP coupler

  1. Hang the new DP/DP coupler on the rail and swing it down.
  2. Screw the DP/DP coupler tight.
  3. Connect the power supply back to the DP/DP coupler. Make sure that you have made the correcting setting on the "PS" DIL switch (see section "Transferring the switch settings ", step 3) .
  4. Insert the bus connector plug in the PROFIBUS DP interface.
  5. Switch on the power supply for the DP/DP coupler.

Further information
A detailed description of the DP/DP coupler is available in the documentation of the DP/DP coupler.

Keywords
DP/DP coupler, exchanging, DIL switch, setting

Related Posts by Categories



Widget by Hoctro | Jack Book
Related Posts with Thumbnails

Our Advertising

Bantuan Pencarian

Jika anda seorang pemula dan tertarik untuk belajar PLC silahkan cek artikel di arsip artikel atau gunakan bantuan pencarian artikel di bawah ini. TQ Bro..

Email Subscribe

Dapatkan informasi dan artikel yang update dari situs ini. Jika anda barminat silahkan masukan email address anda di bawah ini. Terimakasih! (Please write email to subscribe our news).

Enter your email address:

Delivered by FeedBurner

Disclaimer (Privacy Policy)

No PDF Files stored in this site. http://belajarplc.co.nr are not responsible if you download and distribute files or links. Noted that http://belajarplc.co.nr not related in any way with upload files with a copyright material that available for download. Just we collects the information using google search and other search engines links hosted or posted by other website. The link Free Book Download available here are for EDUCATIONAL PURPOSES ONLY... and its recommended to buy the products from the original Owner or Publisher.

For Detail Please Click Here!

Jika anda mempunyai artikel sepurtar dunia automation (PLC dan SCADA) dan ingin sharing buat teman-teman blogger silahkan kirim ke duniaengineering@gmail.com
Terimakasih.

Jika anda menginginkan semua berita yang ada disitus dan links yang ada di situs ini menjadi bagian dari situs yang anda punyai silahkan masukan address ini (copy & paste):
http://feeds2.feedburner.com/belajarplcdanscadaok di fungsi RSS Feeder situs anda.